SIMATIC ET 200eco 16 DIQ DC 24V/0.5A/2A M12-L 8x M12 PN
General information | ||
HW functional status | FS05 | |
Firmware version | V5.1.x | |
FW update possible | Yes | |
Vendor identification (VendorID) | 002AH | |
Device identifier (DeviceID) | 0306H | |
Manufacturer ID according to ODVA (VendorID) | 04E3H | |
Device ID according to ODVA (Product code) | 0FA8H | |
Product function | ||
I&M data | Yes; I&M0 to I&M3 | |
Isochronous mode | No | |
IRT | Yes | |
Prioritized startup | Yes | |
Engineering with | ||
STEP 7 TIA Portal configurable/integrated from version | STEP 7 V17 or higher with HSP 0363 | |
PROFINET from GSD version/GSD revision | GSDML V2.3.x | |
Multi Fieldbus Configuration Tool (MFCT) | from V1.3 SP1 | |
Operating mode | ||
DI | Yes | |
Counter | No | |
DQ | Yes | |
MSI | Yes | |
MSO | Yes | |
Supply voltage | ||
power supply according to NEC Class 2 required | No | |
Load voltage 1L+ | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes; Against destruction; encoder power supply outputs applied with reversed polarity, loads pick up | |
Load voltage 2L+ | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes; against destruction | |
Input current | ||
Current consumption (rated value) | 90 mA; without load | |
from load voltage 1L+ (unswitched voltage) | 12 A; Maximum value | |
from load voltage 2L+, max. | 12 A; Maximum value | |
Encoder supply | ||
Number of outputs | 8 | |
24 V encoder supply | ||
Short-circuit protection | Yes; Group-by-group for 2 channels, electronic | |
Output current, max. | 100 mA; per output | |
Power loss | ||
Power loss, typ. | 9.7 W | |
Address area | ||
Address space per module | ||
Inputs | 2 byte; + 4 bytes for QI information | |
Outputs | 2 byte | |
Hardware configuration | ||
Submodules | ||
Number of configurable submodules, max. | 2 | |
Digital inputs | ||
Number of digital inputs | 16; Parameterizable as DIQ | |
in groups of | 8 | |
Digital inputs, parameterizable | Yes | |
Source/sink input | P-reading | |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes | |
Number of simultaneously controllable inputs | ||
all mounting positions | ||
up to 60 °C, max. | 16 | |
Input voltage | ||
Rated value (DC) | 24 V | |
for signal "0" | -3 to +5V | |
for signal "1" | +11 to +30V | |
Input current | ||
for signal "1", typ. | 2.4 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
parameterizable | Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms | |
Cable length | ||
unshielded, max. | 30 m | |
Digital outputs | ||
Number of digital outputs | 16; Parameterizable as DIQ | |
in groups of | 8; 2 load groups for 8 outputs each | |
Current-sourcing | Yes | |
output type acc. to IEC 61131, type 0.5 | Yes | |
output type acc. to IEC 61131, type 2 | Yes | |
Short-circuit protection | Yes; per channel, electronic | |
Response threshold, typ. | 0.5 A: 1 A / 2 A: 3 A | |
Limitation of inductive shutdown voltage to | 0.5 A: Type 1L+ (-70 V) / 2 A: Type (-18 V) | |
Controlling a digital input | Yes | |
Switching capacity of the outputs | ||
with resistive load, max. | 0.5 A / 2 A | |
with inductive load, max. | 0.5 A / 2 A | |
on lamp load, max. | 0.5 A: 5 W / 2 A 10 W | |
Load resistance range | ||
lower limit | 0.5 A: 48 ohms / 2 A: 12 ohms | |
upper limit | 4 k¦ | |
Output voltage | ||
for signal "1", min. | 1L+ (-0.8 V) / 2L+ (-0.8 V) | |
Output current | ||
for signal "1" rated value | 0.5 A / 2 A | |
for signal "1" permissible range, max. | 0.5 A / 2 A | |
for signal "0" residual current, max. | 0.1 mA | |
Output delay with resistive load | ||
"0" to "1", max. | 0.5 A: 100 µs / 2 A: 150 µs; at rated load | |
"1" to "0", max. | 0.5 A: 150 µs / 2 A: 2.5 ms; at rated load | |
Parallel switching of two outputs | ||
for uprating | No | |
for redundant control of a load | Yes | |
Switching frequency | ||
with resistive load, max. | 0.5 A: 100 Hz / 2 A: 40 Hz | |
with inductive load, max. | 0.5 Hz | |
on lamp load, max. | 1 Hz | |
Total current of the outputs | ||
Current per group, max. | 1L+: 2 A / 2L+: 6 A | |
Current per module, max. | 8 A | |
Cable length | ||
unshielded, max. | 30 m | |
Encoder | ||
Connectable encoders | ||
2-wire sensor | Yes | |
permissible quiescent current (2-wire sensor), max. | 1.5 mA | |
Interfaces | ||
Transmission procedure | 100BASE-TX | |
Number of PROFINET interfaces | 1 | |
1. Interface | ||
Interface type | PROFINET with 100 Mbit/s full duplex (100BASE-TX) | |
Interface types | ||
M12 port | Yes; 2x M12, 4-pin, D-coded | |
Number of ports | 2 | |