Siemens - 6ES7143-6BH00-0BB0

Siemens - 6ES7143-6BH00-0BB0

Regular price €240,93 EUR
Regular price Sale price €240,93 EUR
Sale Sold out

44 in stock

SIMATIC ET 200eco 16 DIQ DC 24V/0.5A/2A M12-L 8x M12 PN

<
General information
HW functional status FS05
Firmware version V5.1.x
FW update possible Yes
Vendor identification (VendorID) 002AH
Device identifier (DeviceID) 0306H
Manufacturer ID according to ODVA (VendorID) 04E3H
Device ID according to ODVA (Product code) 0FA8H
Product function
I&M data Yes; I&M0 to I&M3
Isochronous mode No
IRT Yes
Prioritized startup Yes
Engineering with
STEP 7 TIA Portal configurable/integrated from version STEP 7 V17 or higher with HSP 0363
PROFINET from GSD version/GSD revision GSDML V2.3.x
Multi Fieldbus Configuration Tool (MFCT) from V1.3 SP1
Operating mode
DI Yes
Counter No
DQ Yes
MSI Yes
MSO Yes
Supply voltage
power supply according to NEC Class 2 required No
Load voltage 1L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes; Against destruction; encoder power supply outputs applied with reversed polarity, loads pick up
Load voltage 2L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes; against destruction
Input current
Current consumption (rated value) 90 mA; without load
from load voltage 1L+ (unswitched voltage) 12 A; Maximum value
from load voltage 2L+, max. 12 A; Maximum value
Encoder supply
Number of outputs 8
24 V encoder supply
Short-circuit protection Yes; Group-by-group for 2 channels, electronic
Output current, max. 100 mA; per output
Power loss
Power loss, typ. 9.7 W
Address area
Address space per module
Inputs 2 byte; + 4 bytes for QI information
Outputs 2 byte
Hardware configuration
Submodules
Number of configurable submodules, max. 2
Digital inputs
Number of digital inputs 16; Parameterizable as DIQ
in groups of 8
Digital inputs, parameterizable Yes
Source/sink input P-reading
Input characteristic curve in accordance with IEC 61131, type 3 Yes
Number of simultaneously controllable inputs
all mounting positions
up to 60 °C, max. 16
Input voltage
Rated value (DC) 24 V
for signal "0" -3 to +5V
for signal "1" +11 to +30V
Input current
for signal "1", typ. 2.4 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizable Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms
Cable length
unshielded, max. 30 m
Digital outputs
Number of digital outputs 16; Parameterizable as DIQ
in groups of 8; 2 load groups for 8 outputs each
Current-sourcing Yes
output type acc. to IEC 61131, type 0.5 Yes
output type acc. to IEC 61131, type 2 Yes
Short-circuit protection Yes; per channel, electronic
Response threshold, typ. 0.5 A: 1 A / 2 A: 3 A
Limitation of inductive shutdown voltage to 0.5 A: Type 1L+ (-70 V) / 2 A: Type (-18 V)
Controlling a digital input Yes
Switching capacity of the outputs
with resistive load, max. 0.5 A / 2 A
with inductive load, max. 0.5 A / 2 A
on lamp load, max. 0.5 A: 5 W / 2 A 10 W
Load resistance range
lower limit 0.5 A: 48 ohms / 2 A: 12 ohms
upper limit 4 k¦
Output voltage
for signal "1", min. 1L+ (-0.8 V) / 2L+ (-0.8 V)
Output current
for signal "1" rated value 0.5 A / 2 A
for signal "1" permissible range, max. 0.5 A / 2 A
for signal "0" residual current, max. 0.1 mA
Output delay with resistive load
"0" to "1", max. 0.5 A: 100 µs / 2 A: 150 µs; at rated load
"1" to "0", max. 0.5 A: 150 µs / 2 A: 2.5 ms; at rated load
Parallel switching of two outputs
for uprating No
for redundant control of a load Yes
Switching frequency
with resistive load, max. 0.5 A: 100 Hz / 2 A: 40 Hz
with inductive load, max. 0.5 Hz
on lamp load, max. 1 Hz
Total current of the outputs
Current per group, max. 1L+: 2 A / 2L+: 6 A
Current per module, max. 8 A
Cable length
unshielded, max. 30 m
Encoder
Connectable encoders
2-wire sensor Yes
permissible quiescent current (2-wire sensor), max. 1.5 mA
Interfaces
Transmission procedure 100BASE-TX
Number of PROFINET interfaces 1
1. Interface
Interface type PROFINET with 100 Mbit/s full duplex (100BASE-TX)
Interface types
M12 port Yes; 2x M12, 4-pin, D-coded
Number of ports 2
View full details