1
/
of
1
Siemens - 6ES7231-5PD32-0XB0
Siemens - 6ES7231-5PD32-0XB0
Regular price
€224,39 EUR
Regular price
Sale price
€224,39 EUR
Couldn't load pickup availability
12 in stock
SIMATIC S7-1200 SM 1231 RTD 4 AI RTD
General information | ||
Product type designation | SM 1231, AI 4x16 bit RTD | |
Supply voltage | ||
Rated value (DC) | 24 V | |
Input current | ||
Current consumption, typ. | 40 mA | |
from backplane bus 5 V DC, typ. | 80 mA | |
Power loss | ||
Power loss, typ. | 1.5 W | |
Analog inputs | ||
Number of analog inputs | 4; Resistance thermometer | |
permissible input voltage for voltage input (destruction limit), max. | ±35 V | |
Technical unit for temperature measurement adjustable | Degrees Celsius/degrees Fahrenheit | |
Input ranges | ||
Voltage | No | |
Current | No | |
Thermocouple | No | |
Resistance thermometer | Yes; Resistance-type transmitter: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, LG-Ni1000 | |
Resistance | Yes; 150 Ω, 300 Ω, 600 Ω | |
Input ranges (rated values), resistance thermometer | ||
Cu 10 | Yes | |
Input resistance (Cu 10) | 10 ¦ | |
Ni 100 | Yes | |
Input resistance (Ni 100) | 100 ¦ | |
Ni 1000 | Yes | |
Input resistance (Ni 1000) | 1 000 ¦ | |
LG-Ni 1000 | Yes | |
Input resistance (LG-Ni 1000) | 1 000 ¦ | |
Ni 120 | Yes | |
Input resistance (Ni 120) | 120 ¦ | |
Ni 200 | Yes | |
Input resistance (Ni 200) | 200 ¦ | |
Ni 500 | Yes | |
Input resistance (Ni 500) | 500 ¦ | |
Pt 100 | Yes | |
Input resistance (Pt 100) | 100 ¦ | |
Pt 1000 | Yes | |
Input resistance (Pt 1000) | 1 000 ¦ | |
Pt 200 | Yes | |
Input resistance (Pt 200) | 200 ¦ | |
Pt 500 | Yes | |
Input resistance (Pt 500) | 500 ¦ | |
Input ranges (rated values), resistors | ||
0 to 150 ohms | Yes | |
0 to 300 ohms | Yes | |
0 to 600 ohms | Yes | |
Thermocouple (TC) | ||
Temperature compensation | ||
parameterizable | No | |
Analog value generation for the inputs | ||
Measurement principle | integrating | |
Integration and conversion time/resolution per channel | ||
Resolution with overrange (bit including sign), max. | 15 bit; + sign | |
Integration time, parameterizable | No | |
Interference voltage suppression for interference frequency f1 in Hz | 85 dB at 50 / 60 / 400 Hz | |
Errors/accuracies | ||
Temperature error (relative to input range), (+/-) | 25 °C ±0.1%, to 55 °C ±0.2% total measurement range | |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % | |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | ||
Common mode interference, min. | 120 dB | |
Interrupts/diagnostics/status information | ||
Alarms | Yes | |
Diagnostics function | Yes; Can be read out | |
Alarms | ||
Diagnostic alarm | Yes | |
Diagnoses | ||
Monitoring the supply voltage | Yes | |
Wire-break | Yes | |
Diagnostics indication LED | ||
for status of the inputs | Yes | |
for maintenance | Yes | |
Degree and class of protection | ||
IP degree of protection | IP20 | |
Standards, approvals, certificates | ||
CE mark | Yes | |
CSA approval | Yes | |
UL approval | Yes | |
cULus | Yes | |
FM approval | Yes | |
RCM (formerly C-TICK) | Yes | |
KC approval | Yes | |
Marine approval | Yes | |
Ecological footprint | ||
environmental product declaration | Yes | |
Global warming potential | ||
global warming potential, (total) [CO2 eq] | 43.1 kg | |
global warming potential, (during production) [CO2 eq] | 7.62 kg | |
global warming potential, (during operation) [CO2 eq] | 36 kg | |
global warming potential, (after end of life cycle) [CO2 eq] | -0.544 kg | |
Ambient conditions | ||
Free fall | ||
Fall height, max. | 0.3 m; five times, in product package | |
Ambient temperature during operation | ||
min. | -20 °C | |
max. | 60 °C | |
horizontal installation, min. | -20 °C | |
horizontal installation, max. | 60 °C | |
vertical installation, min. | -20 °C | |
vertical installation, max. | 50 °C | |
Ambient temperature during storage/transportation | ||
min. | -40 °C | |
max. | 70 °C | |
Air pressure acc. to IEC 60068-2-13 | ||
Operation, min. | 795 hPa | |
Operation, max. | 1 080 hPa | |
Storage/transport, min. | 660 hPa | |
Storage/transport, max. | 1 080 hPa | |
Relative humidity | ||
Operation at 25 without condensation, max. | 95 % | |
Pollutant concentrations | ||
SO2 at RH < 60% without condensation | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free | |
connection method | ||
required front connector | Yes | |
Mechanics/material | ||
Enclosure material (front) | ||
Plastic | Yes | |
Dimensions | ||
Width | 45 mm | |
Height | 100 mm | |
Depth | 75 mm | |
Weights | ||
Weight, approx. | 220 g | |
Approvals / Certificates |